Scale and module pairing are the industry risks
Industry partners decide whether to commit printing or module capacity. Printing providers face the scale of the plate: it is 36 times the area of the best printed cooler measured, and 25 to 36 times larger than printed precedents. Channels come out smaller than designed, since a 1 mm channel printed at 988 µm and a horizontal channel at 805 µm. Powder entrapment and material property variation of 18 to 41 percent with annealing add to the risk.
Power-module makers face a pairing problem. Copper expands at 16.5 to 17 ppm/K, aluminum at 22.2 to 25 and silicon carbide at 3.4 to 4, and the strain energy of aluminum silicon carbide is 0.18 MPa against 1.94 for copper and 3.93 for aluminum. The ceramic and the plate must be chosen as a pair. A nickel-phosphorus coating cracked within 1,000 cycles in an analog case, so the plated face of the CF-JET plate needs its own cycling evidence.
Table 2 assigns industry partners a supporting part in the coupon, sub-array and module stages. A printing partner supplies the sub-arrays and coupons, and a module maker supplies the controlled pairs for the final stage.
Decisions and the evidence behind them
Table 10. Decisions for industry partners
| Decision | What the research shows | What is unproven | Evidence |
|---|---|---|---|
| Printing orientation and geometry | Orient orifices along the build direction, add drain and access ports and avoid bends. Process limits are a wall of about 0.3 mm and a fin of about 150 µm | Powder removal at the CF-JET scale | Peer-reviewed measurements; gap stated |
| Pressure budget | A 19.5 percent undersize gives 2.4 times the pressure drop | As-built nozzle diameters from CT data | Computed |
| Module pairing | Aluminum silicon carbide strain energy is 0.18 MPa against 1.94 MPa for copper and 3.93 MPa for aluminum. One plate cycled 1,800 times from −40 to 150 °C without failure | No published life test varies only the cold plate expansion in a silicon carbide module | Peer-reviewed modeling and one test; gap stated |
| Protection of baselines | DFARS 252.227-7017 requires assertions, and SBIR data are protected for 20 years | Proof-of-ownership requirements for software baselines | Regulations; gap stated |
| Market position | Vendors claim 4,000 W single-phase and 4,500 W two-phase cooling, and large infrastructure groups are absorbing cold plate suppliers | Independent test results for the vendor claims | Trade reports and vendor data; unverified |
What to ask the team for
Controlled module pairs that differ only in the cooled base: copper, aluminum silicon carbide and CF-JET.
Cycles with swings of 75 to 125 °C and junction temperatures to 175 °C, with resistance monitored every cycle.
Both failure criteria reported: a 5 percent rise in drain-source voltage and a 20 percent rise in thermal resistance.
A statement of model conditions with every lifetime estimate.
A family of plate areas: 55 cm² at 41.7 W/cm² handles 2,300 W (computed), so a family would cover 700 to 2,300 W.
Frequently asked questions
Can the plate be printed at this size?
The research does not demonstrate it. The best printed cooler measured reached 21 to 35 mm²·K/W on 1 cm², and CF-JET needs 36 times that area. A representative sub-array tested with and without returns is the recommended proof.
How do printed channels differ from the drawing?
A 1 mm channel printed at 988 µm and a horizontal channel at 805 µm. The 19.5 percent undersize of the horizontal case gives 2.4 times the pressure drop (computed), so nozzle sizes should come from measured CT data.
What property variation should a supplier expect?
Material properties varied by 18 to 41 percent with annealing in the research reviewed, so builds should be qualified by measuring the finished plate.
What must a module maker test?
Controlled pairs of modules that differ only in the cooled base, cycled with swings of 75 to 125 °C, with both failure criteria reported and resistance monitored every cycle. The research found no published test that varies only the cold plate expansion.
How are our baselines protected?
Through data-rights assertions under DFARS 252.227-7017, made before award, and through 20 years of SBIR data protection. No source states proof-of-ownership requirements for software baselines.
How do vendor claims compare?
Vendors claim 4,000 W single-phase and 4,500 W two-phase cooling, and no independent test supports either claim. Cold plate suppliers are also being absorbed by large infrastructure groups, which control channels to the largest customers.